Victron Energy MultiPlus-II 48/5000 + Freedom Won LiTE
Closed-loop compatibility, protocol setting and cabling. Best status: verified closed loop.
Field-sourced data. Verify against the current official manual and firmware before commissioning — a wrong setting can damage equipment.
CAN Verified closed-loop confidence: high
- Protocol
- Victron BMS-Can (CAN-bus BMS)
- Inverter setting
- GX: Settings → DVCC ON; Services → VE.Can port → CAN-bus Profile → CAN-bus BMS (500 kbit/s); terminate VE.Can at both ends
- Battery / DIP
- LiTE: straight-through CAT5e from a LiTE RJ45 to the GX CAN port; (eTower needs the supplied 'Victron' cable + master DIP address 01)
Cable
Freedom Won ↔ Victron GX (VE.Can) (LiTE = standard straight-through CAT5e; eTower = supplied 'Victron' cable only)
CAN-bus BMS 500 kbit/s
If the CAN cable is lost or damaged, Victron shuts down within 5 minutes.
Sources
Get the right parts
As an affiliate we may earn a commission from qualifying purchases, at no extra cost to you. This does not affect the compatibility data above.