Solis Solis RHI-6K-48ES-5G + Pylontech US5000
Closed-loop compatibility, protocol setting and cabling. Best status: verified closed loop.
Field-sourced data. Verify against the current official manual and firmware before commissioning — a wrong setting can damage equipment.
CAN Verified closed-loop confidence: high
- Protocol
- Pylontech CAN
- Inverter setting
- CAN protocol: PYLON_LV (NOT the RS485-named one)
- Battery / DIP
- Master address 1 (or 0 depending on brand); CAN into Link Port 0
Wrong choice/cable => Batt_Comm_FAIL / No Battery.
Known errors
| Code | Cause | Fix |
|---|---|---|
| Batt_Comm_FAIL | Old/wrong cable; wrong profile; master address | Updated cable from distributor; select PYLON_LV; master address 1 |